Equipment bay with accommodations for equipment racks
- Two front swing out mounting rack, 22U EIA for 23 wide equipment
- Two rear swing out mounting rack, 22U EIA for 23 wide equipment
- One end bay (OPX-4300 88UX) with stationary 20U EIA rails for AC power distribution, protection mounting and cable input and splicing
- Two end bay (OPX-4300 88UX2) with stationary 20U EIA rails for AC power distribution, protection mounting and cable input and splicing
Access doors that can be padlocked for security
- 2 front, 2 rear, 1 end bay (OPX-4300 88UX)
- 2 front, 2 rear, 2 end bays (OPX-4300 88UX2)
AC load center, 120/240 VAC
AC surge suppressor, 40KA
GFCI outlets
Eltek Valere AC/DC power system to include:
- Rectifier shelf, CA1D-AUN-VC, 5 rectifier positions, 2 bulk outputs
- 23/2U mid mount
- Controller BC2000
- DC breaker panel, 10 position, 2U
- Fuse Panel, 10 position
- AC power and alarm cables
- DC fuses for heat exchangers as required
- DC circuit breakers for equipment
- Remote battery temperature probes
90W/F Heat Exchangers with variable fan speed control board
Intrusion alarm switches on all doors and panels with alarm terminal block and cabling
Four 4” diameter cable entries
Battery deployment pedestal
- Front and rear removable panels that can be padlocked for security
Internal LED light fixture, 48VDC
Grounding provisions
Packaging & Documentation
Options for:
- ADC-Krone 50-pair protection/100-pair punch-down cross-connect panels
- ADC-Krone 10-port solid state Protectors
- 5-pin 200-pair protection panels